HORIZONTAL CEILING SUSPENDED HIDEAWAY TYPE
Casing
- Basic Units is manufactured from galvanized steel sheet.
- Finish can be plain GSS / Pre coated / Powder coated
Cooling coil
Multi row heat transfer coil, 3/8” OD Copper tube, mechanically expanded into Aluminium fins for efficient heat transfer.
Fan Deck : Twin Blowers in Aluminium / GSS construction – Direct driven with a FHP double extended shaft motor. Fan is statically & dynamically balanced.
Fan Motor : Three Speed, permanent split capacitor, single phase motor suitable for 220 V, 50 c/s AC
Filter : 15 mm thick, easily removable, Washable media in GSS frame fitted in a GSS Return air plenum
Drain Pan:
Drain pan is sized to accommodate connected ball valve sets and control valve
Option I : Single skin construction in stainless steel construction with 6 mm thick closed cell insulation
Option II : Double skin construction in galvanized steel sheet with sand witched insulation PUF / Expanded polystyrene in between
Advantages :
- Individual zone control of space temperature
- Prevents cross communication
- No cross talk
- Flexibility to accept future changes in load and space layout
- Occupy no floor space
Applications :
- Hospitality – Guest rooms
- Health Care – Patient rooms
- Offices
- Schools
- Shopping Malls
- Residential Apartments
MODEL NO
CSF - 400
CSF - 600
CSF - 800
CSF - 1000
CSF - 1200
CAPACITY
1.0
1.5
2.0
2.5
3.0
AIR FLOW (CFM)
400
600
800
1000
1200
COIL ROW DEEP
3
3
3
3
4
FIN SPACING
------------------- 12 FINS PER INCH ----------------------
FAN
------------------------- DIDW CENTRIFUGAL, TWIN --------------------
EWT / LWT °F
-------------------------- 44 / 55 --------------------------
WATER FLOW RATE GPM/TR
----------------------- 2.4 ------------------------
OVERALL DIMENSION
L (MM)
1050
1200
1250
1250
1315
D (MM)
575
575
575
650
675
H (MM)
285
285
345
370
370